02.010.0401: Sill Detail – Single Wythe Block This detail shows an 8” (nominal) split face concrete masonry (CMU) wall, window sill condition. Flashing is provided below the masonry sill, returning vertically at the end termination to form and end dam. Ladder-type horizontal joint reinforcement is placed at 16” o.c. vertically in the wall, or as…

02.010.1301: Control Joint – Preformed Gasket

02.010.1301: Control Joint – Preformed Gasket This detail shows specially shaped sash block being used at the vertical control joint, to allow for insertion of a preformed gasket. The gasket is a rigid material, allowing in-plane shrinkage of the block, while providing some resistance to lateral loads. There is horizontal joint reinforcement at 16″ o.c.…

02.120.0752: Plank at Bearing Wall – Interior Wall, Intermediate Elev.

02.120.0752: Plank at Bearing Wall – Interior Wall, Intermediate Elev. This detail shows a precast concrete plank bearing at an interior CMU wall. The wall has horizontal joint reinforcement at 16″ o.c. vertically. The plank has continuous reinforcement and grout at the keyways, and the floor bears on an interior CMU bond beam. The wall…